 Radiator and Duct Mounted Load Banks

Radiator and Duct Mounted Load Bank Model: K711/K711A

K711 Load Bank
*

K711 Sales Bulletin

* K711 Outline Drawings
* K711 Engineering Specifications
The Avtron model K711 and K711A load banks are designed for radiator or duct mounting on diesel engine generator sets. The load bank is permanently mounted to the front of the engine generator and sized to match the width and height of the radiator core or exhaust duct opening. The load bank utilizes the engine cooling air rather than an internal cooling fan found on conventional load banks. A top and bottom mounting flange, or removable duct adapter flanges are supplied for mounting and ease of installation.

The load banks are typically sized at 50-60% of the generator KW rating and used to periodically test the generator or to supplement the real generator load to minimize the effects of diesel engine "wet-stacking".

Helidyne is a trademark of Avtron LoadBank, Inc.

Capacity Minimum Load
Step Resolution
Load Voltage Blower Voltage Size Weight
(lbs.)
10-1000 KW as required 208VAC; 240VAC; 400VAC; 480VAC; 600VAC; 3phase N/A Customer Defined -

^ Back to Top

Note: Other models with different KW and Voltage ratings are available on special order. For high capacity applications such as mounting a 1000 KW load bank to a 2000-2500 KW generator set, the K711L frame can be used.
Control Power: Typical power required for control circuit operation is 120VAC, 1phase, 60 Hz. If 120VAC, 1phase, 60Hz is not available, a variety of single phase control transformers can be provided as an option.
Digital Metering: Avtron Advanced Digital Monitoring System (
* ADMS ™) is available as an option for display of Volts, Amps, Frequency, and KW. Includes Communicator EXT ™ data-logging software.

ADMS is a trademark of Avtron LoadBank, Inc. Communicator EXT is a trademark of Electro Industries/Gauge Tech. Specifications are subject to change without notice.

Home | Contact | Site Map
Load Banks | Industrial Resistors | News | Support | Sales Reps | About Us |
Career Center

Copyright © 1999-2008 Avtron LoadBank, Inc. All rights reserved.

*These are Adobe PDF files. 
Questions on PDF? Visit FAQ's on PDF
*These are Microsoft Word files.